range of product EasyPact
product or component type Circuit breaker
device short name Easypact EZC100N
circuit breaker name Easypact EZC100N
device application Distribution
poles description 4P
protected poles description 3t
network type DC
AC
network frequency 50/60 Hz
[In] rated current 80 A at 40 °C
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2
breaking capacity code N
breaking capacity 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 125 V DC 1P conforming to IEC 60947-2
5 kA Icu at 250 V DC 2P conforming to IEC 60947-2
5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
18 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2
2.5 kA at 250 V DC conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
9 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2
suitability for isolation Yes conforming to IEC 60947-2
utilisation category Category A
trip unit name TM-D
trip unit technology Thermal-magnetic
trip unit rating 80 A at 50 °C
protection type Short-circuit protection
Overload protection
pollution degree 3 conforming to IEC 60947

Complementary

control type Toggle
mounting mode Fixed
mounting support Backplate
upside connection Front
downside connection Front
mechanical durability 8500 cycles
electrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
connection pitch 25 mm
local signalling Positive contact indication
neutral protection setting Without protection
earth-leakage protection Without
height 130 mm
width 100 mm